AGRP Silicone rubber insulation woven wire      AGRP

  • Description
 
   
product features:
 
·Rated voltage:500V
·Temperature Rating:-60℃~+200℃
·Conductor:Tin coated、nickel coated、Silver plated copper wire
·Insulator: silicone rubber
·Apply for high temperment environment such as electrical household appliances, lamps and lanterns, combustion equipment etc.
wire print:   
AGRP 0.3~300mm² 200℃ 500V HUA CHENG CABLE
ITEMS
Technical datas
Applied standard
appearance
smooth,even,without loose
Q/320281ANX01-2006
GB5013.3-1997
spark test
AC5KV /0.15 S
vol. test
1.5KV/1 min
insulation resistance
≥30.5MΩ.KM
Insulation

     Machinery

Performance
before aging
tensile strength
≥5.0N/mm²
break elongation rate
≥150%
after aging
tensile strength
≥4.0N/mm²
 (200±3℃×240h)
break elongation rate
≥120%
poisonous substance control
comply with ROHS rule
EU—2002/95/EC
      
AGRP

spec.

conductor

insulation

thickness of the braid

wire OD

conductor resistance

structure

OD

nominal thickness

min. thickness

OD

nominal diameter

allowance

Ω/KM

mm²

No./mm

mm

mm

mm

mm

mm

mm

mm

below

0.3

17/0.15

0.7

0.5

0.35

1.7

0.15

2.0

+0.20

71.2

-0.10

0.4

23/0.15

0.8

0.5

0.35

1.8

0.15

2.1

+0.20

49.6

-0.10

0.5

28/0.15

0.95

0.5

0.35

1.95

0.15

2.25

+0.20

40.1

-0.10

0.75

24/0.20

1.15

0.5

0.35

2.15

0.2

2.55

+0.20

26.7

-0.10

1.0

32/0.20

1.34

0.5

0.35

2.35

0.2

2.75

+0.20

20.0

-0.10

1.25

40/0.20

1.5

0.6

0.44

2.7

0.2

3.1

+0.20

15.9

-0.10

1.5

30/0.25

1.6

0.6

0.44

2.8

0.2

3.2

+0.20

13.7

-0.10

2.0

41/0.25

1.9

0.6

0.44

3.1

0.2

3.5

±0.20

9.9

2.5

49/0.25

2.0

0.6

0.44

3.2

0.2

3.6

±0.20

8.2

4.0

56/0.30

2.7

0.65

0.485

4.0

0.25

4.5

±0.20

5.09

6.0

84/0.30

3.3

0.7

0.53

4.7

0.25

5.2

±0.20

3.39

10.0

84/0.40

4.6

0.8

0.62

6.2

0.25

6.9

±0.25

1.95

16.0

126/0.40

5.8

0.9

0.71

7.6

0.25

8.1

±0.25

1.24

25.0

196/0.40

7.3

1.0

0.8

9.3

0.30

9.9

±0.25

0.795

35.0

276/0.40

8.6

1.1

0.8

10.8

0.30

11.4

±0.30

0.565

50.0

396/0.40

10.7

1.2

0.98

13.1

0.30

13.7

±0.30

0.393

70.0

360/0.50

12.4

1.2

0.98

14.8

0.30

15.4

±0.30

0.277

95.0

475/0.50

14.5

1.4

1.16

17.3

0.35

18.0

±0.40

0.21

120

608/0.50

16.0

1.6

1.34

19.2

0.35

19.9

±0.40

0.164

150

756/0.50

18.0

1.8

1.52

21.6

0.35

22.3

±0.50

0.132

185

925/0.50

20.0

2.0

1.7

24.0

0.40

24.8

±0.50

0.108

240

1221/0.50

23.0

2.2

1.88

27.4

0.40

28.2

±0.50

0.0817

300

1517/0.50

26.0

2.4

2.06

30.8

0.40

31.8

±0.50

0.0654

                                                                                                                                                                                                                       

Other Products

Product Name:
AGR Silicone Rubber Insulation Installation Wire
Model:
AGR
Description:
·Rated Voltage: 500 V
·Temperature Rating: ≤ 180 ℃
·Conductors: tin copper wire
·Insulator: Silicone Rubber
·Apply to high-temperature environment such as household appliances, lighting, F, H electrical Motors.
Product Name:
SIF-THT SIE-THT silicone rubber insulation wire
Model:
SIF-THT SIE-THT
Description:
·Rated Voltage:300/500V
·Rated temperature:-60℃~+250℃
·Conductor: bare brass or tin-coated copper wire
·Insulator: silicone rubber
Product Name:
FG4G4,UG4G4 silicone rubber double-insulated wire
Model:
FG4G4,UG4G4
Description:
·Rated Voltage:750V
·Rated temperature:180℃
·Conductor: bare brass or tin-coated copper wire
·Insulator: silicone rubber
Product Name:
SIF-GL (H05SJ-K) Fiber Glass Braid Heating-Resisted silicone insulated wire
Model:
SIF-GL (H05SJ-K)
Description:
·Rated Voltage:300/500V
·Rated temperature:-60℃~+180℃
·Conductor: tin-coated or bare brass wire
·Insulator: silicone rubber
fiber glass braid
silicne resin coating
more